'1工程概况…………………………………………………………………………111.1工程概况………………………………………………………………………...111.2设计内容………………………………………………………………………...112设计依据……………………………………………………………………...….112.1设计依据………………………………………………………………………...112.2设计参数………………………………………………………………………...113负荷概算………………………………………………….……………………...113.1用户负荷………………………………………………………………………...113.2负荷汇总………………………………………………………………………...114热交换站设计……………………………………………………………………114.1热交换器……………………………………...…………………………………114.2蒸汽系统…………………………………...……………………………………114.3凝结水系统……………………………………………………………………...114.4热水供热系统…………………………………………………………………...114.5补水定压系统………………………….………………………………………...115室外管网设计……………………………………………………………………115.1管线布置与敷设方式…………………………...………………………………115.2热补偿……………………………………...……………………………………115.3管材与保温……………………………………………………………………...115.4热力入口………………………………………………………………………...11课程作业总结………………………………………………………………………..11参考资料
1工程概况1.1工程概况1.1.2工程名称:某小区供热系统1.1.3地理位置:某地1.1.4热用户:编号1#2#3#4#5#6#建筑面积㎡1210012100121004000480050001.2设计内容某小区换热站及室外热网方案设计2设计依据2.1设计依据《采暖通风与空调设计规范》GB0019-2003《城市热力网设计规范》CJJ34-2002《城镇直埋供热管道工程技术规程》CJJ/T81-98《公共建筑节能设计标准》50189-2005《全国民用建筑工程设计技术措施-暖通空调.动力》-2003《全国民用建筑工程设计技术措施节能专篇-暖通空调.动力》-20072.2设计参数1、外网提供的一次供回水温度是95/702、供回水温度为55/45℃3热负荷概算3.1热用户热负荷概算采用面积热指标法Qn’=qf﹡F×10-2Qn’—建筑物的供暖设计热负荷,单位w;F—建筑物的建筑面积,单位m2qf—建筑物供暖面积热指标,w/m24热交换热站设计4.1换热器4.1.1换热器选型及台数确定1.传热量的确定
计算热负荷(KW)按下式确定Qj=(1.05~1.1)∑Q式中∑Q——累计热负荷,KW;1.05~1.1——考虑损失系数。Qj=1.1∑Q=1.1×5376720W=5914.392KW板式换热器选型计算(K=2000w/m2.k,一次热源温度95/70℃,二次热水温度55/45℃,结垢系数取0.75)逆流:Δt1=95-55=40℃,Δt2=70-45=25℃住宅:5914.4=2000×10^-3×A×(40-25)/In(40/25)换热器面积:A=92.7m24.2.循环水泵选型计算住宅:各选用两台泵,一用一备每台G=462.6m3/h由于换热站到最远的供水点约为800m,沿程阻力按100pa/m,局部阻力按沿程阻力的0.3计算,换热器阻力取60Kpa,过滤器阻力取50Kpa,最不利户内阻力取30Kpa,富裕考虑50kpa;水泵扬程H=0.1×(60+50+104+30+50)=29.4m取1.1~1.2的系数,取32-35m扬程。4.5补水定压4.5.1补水定压方式确定补给水泵的选择(1)扬程:根据保证水压图水静压线的压力要求来确定。H=25.25m(2)流量:一般可按循环水量的3%~5%计算G=4%×=4%×100985.5/1000×=4.039m3/h4.5.2主要设备选型计算选择:1.1G=1.1×4.039=4.44m3/h1.1H=1.1×25.25=28.87mh2O选择2台相同型号低区补水40LG12-15X5G=18m/hN=5.5kwH=60m,其中一台备用。5室外管网设计5.1管线布置与敷设方式1、管网布置原则(1)热源的位置本设计热源为小区内的换热站(2)管网的走向
实际定向时要掌握地质,水文资料,地上,地下构筑物情况,除了技术经济合理外还要考虑维修管理方便,布置时应注意:Ⅰ、管道应尽量穿越负荷区,走向宜平行于建筑物。Ⅱ、尽量少穿越公路,铁路等主要交通干线。Ⅲ、为了施工及管理方便,管线应尽量走绿化地带。Ⅳ、热力管沟外侧与其他建筑物,管线保持一定距离,与基础外边敬距不小于1.5米。Ⅴ、热网规划时应当适当考虑各小区连接方便及小区负荷对称。5.1.2敷设方式3)管道敷设本设计管线全部采用有补偿直埋敷设,采暖管道宜埋于地下水位之上,本设计埋深为1.25米,管道坡度为0.002管道最高处设放气阀,最底处设卸水阀。干管采用有补偿敷设,支管采用无补偿敷设。5.1.3管径确定2、水力计算热水网路水力计算的方法及步骤如下:(1)确定热水网路中各个管段的计算流量:管段的计算流量就是该管段所负担的各个用户的计算流量之和,以此计算流量确定管段的管径和压力损失。对只有供暖热负荷的热水供暖系统,用户的计算流量可用下式计算:—供暖用户的设计热负荷,单位kw;—网路的设计供,回水温度℃C—水的质量比热A—采用不同计算单位的系数,本设计采用A=0.86(3)根据网路主干线各管段的计算流量和初步选用的平均比摩阻R(40~80pa/m)值,利用水力计算表,确定各管段的标准管径和相应的实际比摩阻。(4)热水网路的局部损失,采用当量长度法,将管段的局部阻力损失折合成相当的沿程损失,所以,热水网路中的管段的总压降等于:△P=R(L1+L2)=RLpa式中:L1—管段长度L2—管段当量长度L—管段的折算长度在进行估算时,局部阻力的当量长度L2可从《热水网路局部阻力当量长度表》中查出。(5)根据管段的沿程比摩阻,折算的局部阻力损失和流速,计算管段的总压降。
234561112781090011314室外管网布置简图水利计算表:供水管路水力计算表(80/60℃)管段号热负荷Q(w)流量G(㎏/h)修正后流速流速v(m/s)管径d(mm)修正后管段比摩阻R(Pa/m)管段长度L1(m)局部阻力当量长度L2(m)管段当量长度L(m)管段压力损失△p(Pa)12348500100962.50.8420041.46174.221.21226.322163350070224.51.13150111.5443.517.3660.867409.463108900046816.340.6915052.245014643578.59454450023408.170.5612534.306514.5479.542881.21527225011704.080.4310027.931.56.938.43326.41627225011704.080.4310027.9328.56.635.11071.416’27225011704.080.4310027.93298.2537.251131.47
5’27225011704.080.4310027.9328.2510.25377.254’54450023408.170.5612534.306618.2884.283043.813’108900046816.340.7715052.245018.8968.893892.032’163350070224.51.13150111.5444.518.4562.957642.571’2348500100962.50.8420041.4616.56.4122.911297.22754450023408.170.5612534.30158.6923.69965.28827225011704.080.4310027.931.56.938.43326.41927225011704.080.4310027.9328.56.635.11071.419’27225011704.080.4310027.93298.2537.251131.478’27225011704.080.4310027.9328.2510.25377.257’54450023408.170.5612534.301610.8926.891075.0510715000307380.7012553.5275.710.8986.594870.681151500022139.960.7910093.906010.8570.856960.781227500011822.310.658080.08807.0287.027172.9212’27500011822.310.658080.08818.2989.297354.7011’51500022139.960.7910093.906012.572.57115.7110’715000307380.7012553.5275.710.8986.594870.68132000008598.0420.488045.09307.0137.011781.4213’2000008598.0420.488045.09318.2939.291884.211424000010317.650.548055.67307.0137.012202.4914’24000010317.650.548055.67316.6437.642237.57最大损失∑△P=85275Pa局部阻力当量长度计算表局部阻力形式/管段编号管径d(mm)管段长度L1(m)弯头(m)波纹管补偿器(m)异径接头(m)分(合)流三通直通管(m)分(合)流三通分支管(m)闸阀(m)局部阻力总当量长度(m)1200174.2 4.2215043.5 8.40.56 8.4 17.36315050 8.4 5.6 144125652.27.50.444.4 14.5451001.5 0.33 4.951.656.93610028.51.65 3.3 1.656.66’100291.65 4.95 1.658.255’1002 6.61.658.254’125662.27.50.336.6 1.6518.283’15050 8.40.448.4 1.6518.892’15044.5 8.4 8.4 1.6518.451’20016.54.2 0.56 1.656.41712515 0.44 6.61.658.6981001.5 0.33 4.951.656.93910028.51.65 3.3 1.656.69’100291.65 4.95 1.658.25
8’1002 6.61.658.257’12516 0.44 8.81.6510.891012575.72.2 0.44 6.61.6510.891110060 5.570.333.3 1.6510.851280802.56 0.262.55 1.657.0212’80812.56 0.263.82 1.658.2911’10060 5.570.334.95 1.6512.510’12575.72.2 0.446.6 1.6510.891380301.28 0.26 3.821.657.0113’80311.28 0.26 5.11.658.291480301.28 0.26 3.821.657.0114’80311.28 0.26 5.1 6.645.1.3循环水泵的确定网路循环水泵是驱动热水在热水供热系统中循环流动的机械设备。它直接影响热水供热系统的水力工况。循环水泵的选择对完成集中供热的任务是十分重要的。应着重指出,循环水泵是在闭合环路中工作的,它所需要的扬程仅取决于闭合环路中的总压力损失,而与建筑的高度和地形无关,与定压线高度无关。网路循环水泵工作在封闭的循环回路之中,从它的出口起,即过任何一个用户系统的循环回路,再回到它的入口,其位差所需的压头,正负相抵,综合为零。因此循环水泵的扬程仅消耗在克服热源、网路和用户系统的阻力上,而不需要用它克服用户系统的高度。循环水泵的扬程H=1.1×(Hr+Hw+Hy)(6-2)式中H——循环水泵的扬程;Hr——网路循环水通过热源内部的压力损失;Hw——网路主干线供、回水管的压力损失;Hy——主干线末端用户系统的压力损失,即预留压力。由上面的水力计算表可知:H=1.1×(15+5+2.25)=24.5mh2OG=10.9855m3/h5.2热补偿5.2.1补偿方式选择固定支架,最大允许间距由《集中供热设计手册》查得,补偿器本设计采用套筒补偿器,设置在两固定支架中间,管道的热伸长量不得超过补偿器的补偿量。5.2.2管段热补偿量的计算(只计算干管热补偿量)按以下公式计算管道的热伸长量:m(7-1)式中:--------管道线性膨胀系数,取=12×10-5/m.℃,---------管道的最高使用温度,取80℃;
--------管道安装时的温度,可近似取5℃;--------为两固定支架间距;因为该项目供热面积较小在设计图中用了4对补偿器。算结果如下表:210000043热补偿计算管段标号图热补偿计算表:供回水管段伸长量表管道编号固定支座的间距L(m)管道膨胀系数(m/m.℃)供水管段的最高使用温度℃管道安装时的温度℃供水管道热伸长量L"(m)223.50.0000128050.022562’23.50.0000128050.022563300.0000128050.02883’300.0000128050.02884300.0000128050.02884’300.0000128050.028810400.0000128050.038410’400.0000128050.0384总热补偿量0.23712m干管总伸长量为237.12mm5.2.3固定支座受力计算(只算一个)5.3管材与保温5.3.1管材管道及管件应符合《城镇直埋供热管道工程技术规程》CJJ/T81-98
和《高密度聚乙烯外护管聚氨酯泡沫塑料预制直埋保温管CJ/T114-2000》的要求。管道连接采用焊接连接方式,焊缝坡口和焊接质量应符合相关施工验收规定。5.3.2.保温直埋管道采用预制保温管,采用氰聚塑预制保温管,为增加保温层的耐久性和分辨各种介质的管道,在保护层外涂刷颜色漆,并每隔10左右涂刷分色漆环。5.4热力入口散热器均设温控阀,热力入口均设压差控制阀。详见图纸。课程作业总结参考资料注:1、目录内容及提纲为参考,各位同学可根据自己所做内容及实际情况调整和删减。2、封面为统一封面。《供热工程》
《热网规范》'
您可能关注的文档
- 恒智天成安全计算软件卷扬机牵引力及锚固压重计算书
- 恒智天成安全计算钢结构强度稳定性计算书
- 750kv西永线700方28-32米内悬浮外拉线拉线抱杆设计计算书
- 8.5米高支模扣件钢管楼板模板支架计算书(专家提供支模图计算5.16)
- 手动吊车梁挠度验算计算书
- 挡墙及消防水池计算书
- 新规范混凝土梁挠度验算计算书
- kl50梁模板计算书
- c25水下沉管灌注桩配合比设计计算书.docshu
- 《制冷原理及设备》课程设计计算书
- 《钢筋混凝土结构》课程设计计算书
- 一套完整的工程量计算例子-土木毕业设计(计算书+cad图纸)
- 一套完整的造价计算书(附公式)及建筑面积计算规范
- 一套完整的造价计算书
- 一套完整的造价计算书(附公式)及建筑工程建筑面积计算规范
- 一套完整的造价计算书(附公式)及
- 中华龙山茶室贵宾室结构计算书
- 全隐框玻璃幕墙设计计算书