'QB广东电网公司发布广东电网公司防止电气误操作闭锁装置技术规范Q/GD001.××××.×-2007广东电网公司企业标准2007-XX-XX实施2007-XX-XX发布
Q/GD001.××××.×-2007目次1适用范围···········································································12引用标准···········································································13术语与定义·········································································13.1五防··············································································13.2防止电气误操作闭锁装置····························································13.3变电站自动化系统五防子系统························································23.4微机防误闭锁装置··································································23.5单元电气闭锁······································································23.6防误闭锁软件系统··································································23.7解锁工具Ⅰ
Q/GD001.××××.×-2007··········································································23.8智能解锁钥········································································23.9万能解锁钥匙······································································23.10逻辑表············································································24技术要求···········································································34.1基本要求··········································································34.2电气闭锁技术要求··································································34.3微机防误闭锁装置的技术要求························································35配置原则···········································································75.1配置基本原则······································································85.2变电站的断路器、隔离开关、接地开关(接地线)、网门的防误配置·······················86接地桩技术规范·····································································9Ⅰ
Q/GD001.××××.×-20076.1接地桩设置要求····································································96.2接地桩的布点要求··································································96.3接地桩的编号原则··································································107五防闭锁逻辑·······································································107.1五防闭锁逻辑制定原则······························································107.2通用闭锁逻辑的要求································································107.3典型闭锁逻辑关系··································································11附录A500kV线—变串典型逻辑关系(二分之三接线类型)··································13附录B500kV线—线串典型逻辑关系(二分之三接线类型)··································15附录C500kV主变220kV侧典型逻辑关系·················································17附录D220kV主变典型逻辑关系(双母分段接线方式)······································18附录E220kV(110kV)线路典型逻辑关系(双母分段接线方式)····························20Ⅰ
Q/GD001.××××.×-2007附录F35kV侧典型逻辑关系(单母接线方式)·············································21附录G220kV(110kV)母线地刀和PT间隔典型逻辑关系···································23附录H220kV(110kV)母联或分段间隔典型逻辑关系······································24附录I220kV(110kV)线路典型逻辑关系(双母带旁路接线类型)···························25附录J220kV(110kV)专用旁路间隔典型逻辑关系(双母带旁路接线类型)···················26附录K双母带旁路类接线:主变间隔逻辑关系·············································27附录L单母分段小车开关类型接线:10kV(35kV)线路、分段典型逻辑关系····················29附录M单母分段小车开关接线类型:电容器组及其网门典型逻辑关系·························30附录N单母分段小车开关接线类型:站变(接地变)及其网门典型逻辑关系···················31附录O单母分段带旁路接线类型:出线、分段、旁路间隔典型逻辑关系·······················32附录P线路变压器组接线图:线变组典型逻辑关系·········································33附录Q桥型接线类:110kV桥型接线典型逻辑关系·········································34附录R接地桩形式图·································································36附录S接地桩布置图·································································37附录T接地桩编号原则Ⅰ
Q/GD001.××××.×-2007·······························································38Ⅰ
Q/GD001.××××.×-2007前言防止电气误操作闭锁装置是变电站的重要设备,是防止电气误操作的必备技术手段。为了明确广东电网公司变电站防止电气误操作闭锁装置的配置规范,明确各类防止电气误操作闭锁装置的技术要求,指导变电站防止电气误操作闭锁装置的建设、改造,确保防止电气误操作闭锁装置满足变电站防止误操作要求,有效防止电气误操作的发生,特制定本规范。本规范附录A-附录Q为规范性附录,附录R-附录T为资料性附录。本规范由广东电网公司生产技术部提出、归口及解释。本规范由下列人员起草:林玮玲、林乐彤、李端姣、陈曦、赵永发、梁广、胡日鹏、王磊、吴俊、刘汉君、张华庆、陈展尘审核:马辉王政源审定:张文峰李哲批准:徐达明本规范自2007年10月1日起实施。执行中的问题和意见,请及时反馈给广东电网公司生产技术部。Ⅲ
Q/GD001.××××.×-2007Ⅲ
Q/GD001.××××.×-2007广东电网公司防止电气误操作闭锁装置技术规范1适用范围1.1本规范适用于广东电网公司下属变电站防止电气误操作闭锁装置(以下简称防误装置)的建设和改造。1.2变电站自动化系统五防子系统的技术要求参照《广东电网变电站自动化系统五防子系统功能验收规范》执行。2引用标准下列文件中的条款通过本规范的引用而成为本规范的条款。凡是注日期的引用文件,其随后所有的修改单(不包括勘误的内容)或修订版均不适用于本规范,然而,鼓励根据本规范达成协议的各方研究是否可使用这些文件的最新版本。凡是不注日期的引用文件,其最新版本适用于本规范。JB/DQ2181—87高压开关设备用电磁锁技术条件JB/DQ2182—87高压开关设备用机械锁通用技术条件SD334—89高压带电显示装置技术条件DL/T687-1999微机型防止电气误操作装置通用技术条件Q/CSG10006-2004电气操作导则中国南方电网有限责任公司防止电气误操作闭锁装置管理规定(2005年3月)Q/GD001.1126.02-20075广东电网变电站自动化系统五防子系统功能验收规范3术语与定义3.1五防指防止误入带电间隔、防止带负荷误拉(合)隔离开关、防止带接地开关(接地线)合隔离开关、防止带电合(挂)接地开关(接地线)、防止误分合断路器等五项防止电气误操作。3.2防止电气误操作闭锁装置11
Q/GD001.××××.×-2007为满足变电站五防要求,在电气设备及其自动化控制系统上安装的对电气设备操作流程、操作位置进行闭锁和提示的装置,包括变电站自动化系统五防子系统、微机防误闭锁装置、电气闭锁、电磁闭锁、机械联锁、机械程序锁等。1.1变电站自动化系统五防子系统指变电站自动化系统中用于实现五防闭锁的功能模块及相应电脑钥匙、锁具等构成的子系统。1.2微机防误闭锁装置采用微型计算机控制,用于变电站电气设备防止电气误操作的装置。通常由防误计算机、防误闭锁软件系统、电脑钥匙、锁具、解锁钥匙和模拟屏(可选)等功能元件组成。1.3单元电气闭锁指通过二次电缆连接,将间隔内关联电气设备位置状态转化为对电气设备操作流程进行闭锁。在本规范中指用于本间隔内电动隔离开关(接地开关)、断路器之间的电气闭锁,以及为完成线路倒闸操作所必需的母线接地开关与线路隔离开关之间跨间隔的电气闭锁。1.4防误闭锁软件系统指能够反映变电站电气设备位置状态,并按变电站五防要求控制变电站自动化系统操作或控制电气、机械编码锁具操作的软件系统。1.5解锁工具指防误闭锁装置异常或电网、设备处于紧急状态时,用于强制解除闭锁的专用工具或程序指令。1.6智能解锁钥匙指通过手工输入解锁对象的设备编号,或通过画面点选该设备的方式,确定唯一的解锁对象的解锁钥匙,具有多级密码权限管理。1.7万能解锁钥匙指可以开任一把锁的解锁钥匙。1.8逻辑表指根据变电站五防要求,反映全站高压电气设备间闭锁关系的表。11
Q/GD001.××××.×-20071技术要求1.1基本要求4.1.1所有高压电气设备,均应装设对电气一次设备进行强制闭锁的防误装置,装置的性能和质量应符合产品标准与本规范的要求。4.1.2防误装置的结构应简单、可靠,操作维护方便。4.1.3防误装置应不影响断路器、隔离开关和接地开关等设备的主要技术性能(如合闸时间、分闸时间、速度、操作传动方向角度等)。4.1.4防误装置的工作电源必须采用不间断供电方式,并由独立回路供电。4.1.5防误装置应做到防腐、防锈、抗干扰、防异物开启。户外的防误装置还应防水、耐低温、耐高温。4.1.6防误装置五防功能中除防止误分合断路器可采用提示性方式,其余"四防"必须采用强制性方式。4.1.7防误装置应有专用的解锁工具。4.1.8断路器的机械紧急事故跳闸脱扣不允许闭锁。4.1.9防误装置应选用符合国家、行业技术标准、并经省级以上鉴定的产品。已通过鉴定的防误装置,必须经运行考核合格,取得良好的试运行经验后方可推广使用。4.1.10新型防误装置的试用应经广东电网公司同意后才可试用。1.2电气闭锁技术要求4.2.1电气闭锁与微机防误闭锁装置相互配合,共同完成隔离开关闭锁,正常操作时,二者之间逻辑为“与”的关系。4.2.2断路器和隔离开关电气闭锁回路应直接采用断路器和隔离开关的辅助接点,严禁使用重动继电器。1.3微机防误闭锁装置的技术要求4.3.1防误计算机的技术要求防误计算机应实现与变电站自动化系统的通讯,PC机配置不得低于以下要求:a)CPU:P4-2G或以上11
Q/GD001.××××.×-2007a)内存:256M或以上b)硬盘:40G或以上c)显卡:32M或以上显存的AGP图形加速卡d)显示器:具备TCO99认证的17英寸纯平或以上彩显。e)打印机:A4激光打印机4.3.2防误闭锁软件系统的技术要求4.3.2.1防误闭锁软件应具备操作票编辑功能,操作票的生成应包括以下三种方式:a)打开编辑界面直接编辑生成。b)在主接线图上进行模拟操作生成。c)从模板票、典型票或历史票导入生成。4.3.2.2操作票的编辑界面应友好方便,能根据现场运行需求增加或删除操作步骤,接地桩、网门、相关二次设备的状态等应能纳入操作票。4.3.2.3防误闭锁软件应能设置开票时是否自动对“合/分”操作进行“检合/检分”操作。4.3.2.4模板票宜分为通用模板和专用模板两种(通用模板是同一设备组类型下相同设备子类型的所有设备的操作票模板,如进线设备组下进线断路器的操作票模板;专用模板是指某个固定设备的操作票模板,如进线断路器101的操作票模板)。通用模板票应用到不同间隔就可以开出不同操作票,对于相同接线和设备的同电压等级的间隔只需开一套通用模板票,降低典型操作票的设置工作量。4.3.2.5防误闭锁软件应允许将操作票预先开好、完成预演,转为可执行的操作票时必须自动进行规则校验,如未通过规则校验,则拒绝执行并提示错误信息。4.3.2.6操作票应支持手动预演和自动预演两种方式。4.3.2.7应有完善的操作权限设置功能,应至少支持管理员、操作员、监护人三种以上的权限分类,其操作权限应可根据运行需求灵活调整。五防退出、逻辑编辑修改应有独立的权限管理。4.3.2.8操作票查询显示窗应可以按电压等级、设备组或指定条件显示归档票和模板票的任务列表和内容。4.3.2.9操作票应能按预开、作废、已执行分类保存及显示。11
Q/GD001.××××.×-20074.3.2.10操作票统计表应包括操作票日报表、月报表、季度报表、年报表以及五防锁具统计表等常用表格,并能根据时间、人员、操作对象等指定条件定制统计表。4.3.2.11操作票应具备打印功能,标题、单位标志、操作内容等应能灵活设置。4.3.2.12操作票票号应由程序自动按顺序生成,不可更改,按页数调整票号,输出增加一页,编号加一。4.3.2.13五防功能需退出时应按间隔设置,禁止全站退出五防功能。4.3.2.14防误闭锁软件应提供五防逻辑规则编辑功能,在规则校验时应根据输入的规则来判断操作是否允许执行,以防止误操作。操作规则库应类型多样、定义灵活,支持必要条件规则、充分条件规则、通用规则、一般规则、并(或)条件存在、提示性操作条件等。可根据用户需求增加、删去、修改各逻辑规则。4.3.2.15五防规则编辑工具应使用方便、操作直观,宜采用用户界面友好的图形化的规则编制界面,也可采用文本规则编制界面。两种方式均应支持复制五防规则等手段,减少五防规则的设置工作量。系统应具备五防规则导入导出功能。4.3.3电脑钥匙的技术要求4.3.3.1外型设计应美观、合理,便于单手握持;具备背光照明功能,满足夜间操作需要;具备汉字显示功能,可随用户要求编程不同的提示语句,并满足双编号的操作提示要求;具备汉语语音功能。4.3.3.2电脑钥匙是五防系统中的一个关键装置,应能正确无误地接收五防主机下装的操作票。4.3.3.3电脑钥匙应能够记忆存储当前执行的操作票,关闭电源及更换电池时,内容不丢失。4.3.3.4每把电脑钥匙只能接受一个操作任务,五防计算机允许有多组没有逻辑关系的倒闸操作任务。4.3.3.5电脑钥匙具有口令设置、试听语音、调节液晶对比度、背光、电池电量显示、锁编码检查、中止当前的操作票、跳步等功能。4.3.3.6电脑钥匙宜采用五防主机自动对时技术,接收五防主机发来的对时信息。4.3.3.7电脑钥匙宜可记录每步操作的时间,回送到五防主机保存,可对操作过程进行分析、评估。11
Q/GD001.××××.×-20074.3.3.8在任一步骤操作开始前或结束后,电脑钥匙应均可游览操作票前后各项的内容,为实际操作提供了便利。必要时,应可对电脑钥匙存储的操作步骤进行跳步和中止操作,但必须通过严格的口令验证,具备权限管理手段。4.3.3.9电脑钥匙宜具备对当前操作设备具有重复开锁的功能,但不能对上一步操作设备进行重复开锁。4.3.3.10电脑钥匙应有多种属性的操作:a)能接通电气编码锁。b)能开机械编码锁。c)显示提示性操作,可以把不需要强制闭锁的设备,作为提示性属性。4.3.3.11电脑钥匙与锁具应顺畅配合,无卡涩现象,保证能在符合条件时顺利开锁。4.3.3.12应配备智能解锁钥匙和万能解锁钥匙各一套,确保在紧急情况下对各类锁具进行强制解锁。4.3.3.13电脑钥匙应满足如下技术指标:a)工作环境温度:-10℃~+50℃;b)识别并编码锁个数≥1000把;c)单次开锁成功率:≥99%(即连续开锁100次,成功开锁次数应在99次以上);d)一次可接收操作内容≥200项;e)一次充足电可连续开锁个数≥500把;f)通信连接方式:串口、USB、红外、蓝牙;g)下载操作票成功率≥99%;h)下载操作票时间≤1分钟(操作票的内容小于50项时);i)平均无故障时间(MTBF)≥2年。4.3.3.14变电站应配置两把电脑钥匙。4.3.4锁具的技术要求4.3.4.1锁具材质优良、防尘、防锈、无卡滞;户外锁具还应防水、防潮、防霉。4.3.4.2各锁具与电脑钥匙配合良好。11
Q/GD001.××××.×-20074.3.4.3锁具应满足如下技术指标:a)工作环境温度:-10℃~+70℃b)平均无故障时间(MTBF)≥2年c)单次被开锁成功率≥99%(即连续被开锁100次,成功被开锁次数应在99次以上)4.3.5模拟屏的技术要求4.3.5.1模拟屏上电气主接线图上为全站一次系统图,主接线图应与变电站一次系统布置相同,并按变电站最终规模制作。4.3.5.2模拟屏上的图形按电力系统符号标准,线条及符号颜色按照电压等级执行如下:500kV330kV220kV110kV35kV13.8kV10kV0.4kV淡黄白紫朱红鲜黄浅绿紫红黄褐4.3.5.3模拟屏屏面材料须采用具有高阻燃性能的工程塑料注塑而成的活面镶嵌式马赛克块,规格25×25mm,屏面应变形小,光洁度高、不反光,且组合方便,能够方便地对一次主接线图进行修改。模拟屏的颜色应符合控制室环境氛围。屏体背面采用活动式推拉门,方便安装及检修。4.3.5.4模拟屏如为旋钮开关马赛克屏,屏上用于显示一次设备状态的元件为旋钮式开关,通过开关分、合位置表示现场一次设备的运行(分合)状态,应直观清晰,符合运行人员操作习惯,其变位必须经人工扳动。4.3.5.5模拟屏如为触摸灯开关马赛克屏,屏上用于显示一次设备状态的元件为触摸式灯开关,通过不同的颜色表示不同的运行状态,其变位由灯开关控制器根据工控机发出的指令自动实现,无须运行人员干涉。4.3.5.6模拟屏应具有在线对位功能:利用旋钮开关或灯开关在屏面上实时显示相关设备状态,旋钮开关模拟屏的对位需在智能语音的提示下通过手动对位;触摸灯开关式模拟屏应实现与现场一次设备自动实时在线对位并具有远方操作后或事故动作后自动刷屏的功能。4.3.5.7模拟屏须具有汉字操作提示功能。4.3.5.8模拟屏具有智能语音报警功能和仿真操作培训功能。1配置原则11
Q/GD001.××××.×-20071.1配置基本原则5.1.1新建以及全站进行综合自动化改造的变电站,原则上应采用变电站自动化系统五防子系统加单元电气闭锁。5.1.2运行中变电站防误装置的改造,原则上应采用微机防误闭锁装置加单元电气闭锁,或变电站自动化系统五防子系统加单元电气闭锁。5.1.3成套高压开关设备(包括GIS设备、封闭式开关柜、小车柜)自身应具有完善的机械联锁或电气闭锁。1.2变电站的断路器、隔离开关、接地开关(接地线)、网门的防误配置5.2.1断路器配置以下的闭锁方式实现闭锁。5.2.1.1对在变电站主控室操作,如采用变电站自动化系统的变电站,站控层操作应通过微机防误闭锁软件来实现闭锁,测控屏操作应配置微机防误电气编码锁来实现闭锁;如采用常规RTU变电站,控制屏操作应配置微机防误电气编码锁来实现闭锁。5.2.1.2对在变电站设备现场操作,10kV断路器应配置微机防误电气编码锁来实现闭锁。5.2.2电动机构的隔离开关、接地开关配置以下的闭锁方式实现闭锁5.2.2.1对在变电站主控室操作,如采用变电站自动化系统的变电站,站控层操作应通过微机防误闭锁软件及测控装置闭锁来实现闭锁;如采用常规RTU变电站,控制屏操作应配置微机防误电气编码锁来实现闭锁。5.2.2.2对在敞开式变电站远方控制箱操作,应配置微机防误电气编码锁以及单元电气闭锁来实现闭锁。5.2.2.3对在隔离开关、接地开关的机构箱操作,可在机构箱门上配置微机防误机械编码锁来实现闭锁。5.2.3手动机构的隔离开关、接地开关应在操作机构上配置微机防误机械编码锁来实现闭锁。5.2.4变电站接地桩应安装微机防误机械编码锁。5.2.5高压开关柜及间隔式配电装置(间隔)有网门(如电容器组、电抗器、消弧线圈等)时,应安装微机防误装置的机械编码锁,宜在网门上安装带电显示装置。11
Q/GD001.××××.×-20071接地桩技术规范1.1接地桩设置要求6.1.1采用微机防误闭锁装置的新建、扩建或改造变电站的接地桩必须配置机械编码锁,并纳入五防逻辑管理。运行中的变电站应结合综自改造或专项改造项目逐步完成对接地桩加装机械编码锁的改造。6.1.2接地桩的设计必须满足与接地线连接方便、牢固,接触面满足接地点短路电流的要求。6.1.3接地桩一般设在设备支柱底部最靠近接地设备的位置。6.1.4每个接地桩及其机械编码锁都应贴有铝制的印有接地桩编号的标签,标签应带边框。6.1.5接地桩的形式可参考附录R。1.2接地桩的布点要求6.2.1原则上变电站内所有可能使用接地线进行接地的接地点都必须设置接地桩,除母线外同一个电气节点一般只设一个接地桩,如果同一电气节点的实际位置相差较远或中间有解线可能,则可根据实际需要增设接地桩数量。6.2.210kV及以上户外敞开式断路器两侧、隔离开关靠线路侧、隔离开关靠主变侧均应装设接地桩,其位置宜安装于原有的接地开关附近。6.2.310kV及以上户外每一段敞开式母线如果长度超过10米则应在母线的两端设置接地桩,如果不到10米则可只设一个接地桩,接地桩的位置宜安装在原有的母线接地开关附近,如果没有母线接地开关的可在PT隔离开关的母线侧安装,具体位置应考虑现场实际情况和操作方便后确定。6.2.4变压器(包括主变压器、接地变及站变)各侧套管出线处均需设接地桩,接地桩安装于变压器各侧附近接地极上,具体位置应考虑现场实际情况和操作方便后确定。6.2.510kV小车开关柜的各段母线应设接地桩,接地桩宜设置于各段母线PT柜外底部附近的接地极上。6.2.610kV小车开关柜馈线柜一般不装设接地桩,如电缆头的检修或更换CT工作需要频繁接地,也可根据需要在每个开关柜后装设接地桩。6.2.7对于10kVXGN柜的断路器两侧、线路隔离开关线路侧(或主变隔离开关主变侧)三处位置若没有安装接地开关,应在相应位置附近分别装设接地桩。11
Q/GD001.××××.×-20076.2.810kVGG1A柜的断路器两侧、线路隔离开关线路侧(或主变隔离开关主变侧)三处位置应分别装设接地桩,不同的接地桩可相邻,但机械编码锁应分别独立。6.2.910kVGG1A母线PT柜宜分别设置母线接地桩和PT高压侧接地桩,机械编码锁应分别独立。6.2.1010kV电容器组的接地桩宜安装于进线电缆头和中性点接地位置附近接地极上,具体位置应考虑现场实际情况和操作方便后确定。6.2.11线路耦合电容器或电压式互感器靠线路出变电站侧,可根据检修需要增加接地桩。6.2.12接地桩布点图可参考附录S。1.1接地桩的编号原则各下属供电局可根据具体情况编制本局的接地桩编号原则,编号原则可参考附录T。2五防闭锁逻辑2.1五防闭锁逻辑制定原则闭锁逻辑必须满足且仅需满足“五防”的要求。2.2通用闭锁逻辑的要求7.2.1断路器通用闭锁逻辑:无条件分合闸。7.2.2隔离开关通用闭锁逻辑:7.2.2.1对于双母线类接线,只有母联断路器及其两侧隔离开关合上时才允许倒母线。7.2.2.2除倒母线外,断路器间隔内的隔离开关应在断路器分闸后才能分合闸。7.2.2.3合隔离开关时,隔离开关两侧接地开关应分开、接地线应拆除,包括经断路器、主变、接地变/站变、电缆等连接的接地开关及接地线。7.2.2.4旁路断路器间隔的旁路隔离开关,必须旁路断路器分开,旁路母线接地开关分开的状态下才能合闸。7.2.2.5非旁路断路器间隔的旁路隔离开关,必须在旁路断路器分开、旁路母线上所有接地开关分开、所在间隔线路侧接地开关(主变各侧接地开关)在分开的状态下才能合闸。7.2.2.6母线接地开关合上或母线接上接地线后,母线上的各隔离开关、小车均不能合上。7.2.2.7小车的位置规则与隔离开关规则一致。11
Q/GD001.××××.×-20077.2.3接地开关(接地线)通用闭锁逻辑:7.2.3.1接地开关无条件分闸。7.2.3.2主变中性点接地开关无条件分合闸。7.2.3.3合接地开关或接接地线时,与接地开关直接相连或经断路器、主变、接地变/站变、电缆等连接的隔离开关必须在分闸位置、小车必须在试验位置。7.2.3.4母线上的所有隔离开关、小车拉开后,才能合上母线接地开关或在母线上接接地线。7.2.3.5线路如果有带电闭锁装置或闭锁接点,则合线路接地开关或接接地线时,除与接地开关直接相连或经断路器连接的隔离开关必须在分闸位置、小车必须在试验位置,还必须判断所在的线路不带电。7.2.3.6接地线的分合规则与相应位置处的接地开关分合通用闭锁逻辑相同。7.2.3.7电容器与串联电抗器之间、电容器中性点的接地开关或接地线的闭锁逻辑与电容器组进线接地开关的规则相同。7.2.4网门闭锁逻辑7.2.4.1一般要求网门内设备的所有有电荷或有来电可能的地方都要接地,才能打开网门。包括站变(或接地变)的两侧,电容器组的进线侧和中性点位置均要接地。7.2.4.2一般要求网门内的接地线拆除后,才能关上网门。1.1典型闭锁逻辑关系7.3.1二分之三接线类型:500kV线-变串典型逻辑关系见附录A、500kV线-线串典型逻辑关系见附录B、500kV主变220kV侧典型逻辑关系见附录C。7.3.2双母分段接线类型:220kV主变各侧隔离开关典型逻辑关系见本文附录D、220kV(110kV)线路典型逻辑关系见附录E、220kV(110kV)母线地刀和PT典型逻辑关系见附录F、220kV(110kV)分段或母联间隔典型逻辑关系见附录G。7.3.3单母接线类型:35kV侧隔离开关典型逻辑关系见附录H。7.3.4双母带旁路接线类型:220kV(110kV)线路典型逻辑关系见附录I、220kV(110kV)旁路间隔典型逻辑关系见附录J、220kV(110kV)主变各侧隔离开关典型逻辑关系见附录K。11
Q/GD001.××××.×-20077.3.5单母分段小车开关接线类型:10kV线路、分段典型逻辑关系见附录L、电容器组及其网门典型逻辑关系见附录M、站变(接地变)及其网门典型逻辑关系见附录N。7.3.6单母带旁路接线类型:出线、分段、旁路间隔典型逻辑关系见附录O。7.3.7线变组类型接线:线变组典型逻辑关系见附录P。7.3.8桥型接线:桥型组典型逻辑关系见附录Q。11
附录A500kV线-变串典型逻辑关系(二分之三接线类型)接线类别500kV线-变串典型逻辑关系(二分之三接线类型)接线示意图编号含义1M2M1M2M母线Q0ABCABC开关Q1Q21M2M刀闸Q6CC开关主变侧刀闸Q51CC开关母线侧地刀Q52CC开关CT侧地刀Q61B开关线路侧刀闸Q62B开关主变侧刀闸Q51BB开关IM侧地刀Q52BB开关2M侧地刀Q6AA开关线路侧刀闸Q51AA开关母线侧地刀Q52AA开关CT侧地刀Q53A线路侧地刀Q53C主变侧地刀Q26Q252M地刀Q16Q151M地刀逻辑关系1.开关A、B、C闭锁逻辑:分闸合闸无条件。2.1M母线侧刀闸Q1闭锁逻辑:合闸条件:1M所有地刀Q15、Q16分,线路开关Q0A分,线路开关A两侧地刀Q51A、Q52A分;分闸条件:线路开关Q0A分。3.2M母线侧刀闸Q2闭锁逻辑:合闸条件:2M所有Q25、Q26地刀分,主变开关Q0C分,主变开关C两侧地刀Q51C、Q52C分;分闸条件:主变开关Q0C分。4.B开关线路侧刀闸Q61闭锁逻辑:合闸条件:线路侧地刀Q53A分,开关Q0B分,开关B两侧地刀Q51B、Q52B分;分闸条件:开关Q0B分。5.B开关主变侧刀闸Q62闭锁逻辑:合闸条件:主变三侧地刀分,开关Q0B分,开关B两侧地刀Q51B、Q52B分;分闸条件:开关Q0B分。6.A开关线路刀闸Q6A闭锁逻辑:合闸条件:线路侧地刀Q53A分,线路开关Q0A分,线路开关A两侧地刀Q51A、Q52A分;37
分闸条件:线路开关Q0A分。7.C开关主变侧刀闸Q6C闭锁逻辑:合闸条件:主变三侧地刀分,主变开关Q0C分,主变开关C两侧地刀Q51C、Q52C分;分闸条件:主变开关Q0C分。8.线路侧地刀Q53A闭锁逻辑:合闸条件:A开关线路侧刀闸Q6A分,B开关线路侧刀闸Q61分,线路无电;分闸条件:无。9.主变侧地刀Q53C闭锁逻辑:合闸条件:C开关主变侧刀闸Q6C分,B开关主变侧刀闸Q62分,主变其余各侧刀闸分开(无电);分闸条件:无。10.A开关两侧地刀Q51A、Q52A闭锁逻辑:分闸条件:无;合闸条件:A开关两侧刀闸Q1、Q6A分开。11.B开关两侧地刀Q51B、Q52B闭锁逻辑:分闸条件:无;合闸条件:B开关两侧刀闸Q61、Q62分开。12.C开关两侧地刀Q51C、Q52C闭锁逻辑:分闸条件:无;合闸条件:C开关两侧刀闸Q2、Q6C分开。13.1M母线地刀Q15Q16闭锁逻辑:分闸条件:无;合闸条件:1M母线上所有1M侧刀闸分开。14.2M母线地刀Q25Q26闭锁逻辑:分闸条件:无;合闸条件:2M母线上所有2M侧刀闸分开。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录B500kV线-线串典型逻辑关系(二分之三接线类型)接线类别500kV线-线串典型逻辑关系(二分之三接线类型)接线示意图编号含义1M2M1M2M母线Q0ABCABC开关Q1Q21M2M刀闸Q6CC开关线路侧刀闸Q51CC开关母线侧地刀Q52CC开关CT侧地刀Q61B开关线路1侧刀闸Q62B开关线路2侧刀闸Q51BB开关I母侧地刀Q52BB开关2母侧地刀Q6AA开关线路侧刀闸Q51AA开关母线侧地刀Q52AA开关CT侧地刀Q53A线路1线路侧地刀Q53C线路2线路侧地刀Q26Q252M地刀Q16Q151M地刀逻辑关系1.线路开关A、B、C闭锁逻辑:分闸合闸无条件。2.1M母线侧刀闸Q1闭锁逻辑:合闸条件:1M所有地刀Q15、Q16分,线路开关Q0A分,线路开关A两侧地刀Q51A、Q52A分;分闸条件:线路开关Q0A分。3.2M母线侧刀闸Q2闭锁逻辑:合闸条件:2M所有Q25、Q26地刀分,线路开关Q0C分,线路开关C两侧地刀Q51C、Q52C分;分闸条件:线路开关Q0C分。4.B开关线路1侧刀闸Q61闭锁逻辑:合闸条件:线路1线路侧地刀Q53A分,线路开关Q0B分,线路开关B两侧地刀Q51B、Q52B分;分闸条件:线路开关Q0B分。5.B开关线路2侧刀闸Q62闭锁逻辑:合闸条件:线路2线路侧地刀Q53C分,线路开关Q0B分,线路开关B两侧地刀Q51B、Q52B分;分闸条件:线路开关Q0B分。6.A开关线路1侧刀闸Q6A闭锁逻辑:合闸条件:线路1线路侧地刀Q53A分,线路开关Q0A分,线路开关A两侧地刀Q51A、Q52A分;分闸条件:线路开关Q0A分。7.C开关线路2侧刀闸Q6C闭锁逻辑:合闸条件:线路2线路侧地刀Q53C分,线路开关Q0C分,线路开关C两侧地刀Q51C、Q52C分;分闸条件:线路开关Q0C分。8.线路1线路侧地刀Q53A闭锁逻辑:合闸条件:A开关线路1侧刀闸Q6A分,B开关线路1侧刀闸Q61分,线路无电;37
分闸条件:无。9.线路2线路侧地刀Q53C闭锁逻辑:合闸条件:C开关线路2侧刀闸Q6C分,B开关线路2侧刀闸Q62分,线路无电;分闸条件:无。10.A开关两侧地刀Q51A、Q52A闭锁逻辑:分闸条件:无;合闸条件:A开关两侧刀闸Q1、Q6A分开。11.B开关两侧地刀Q51B、Q52B闭锁逻辑:分闸条件:无;合闸条件:B开关两侧刀闸Q61、Q62分开。12.C开关两侧地刀Q51C、Q52C闭锁逻辑:分闸条件:无;合闸条件:C开关两侧刀闸Q2、Q6C分开。13.1M母线地刀Q15Q16闭锁逻辑:分闸条件:无;合闸条件:1M母线上所有1M侧刀闸分开。14.2M母线地刀Q25Q26闭锁逻辑:分闸条件:无;合闸条件:2M母线上所有2M侧刀闸分开。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录C500kV主变220kV侧典型逻辑关系接线类别500kV主变220kV侧典型逻辑关系接线示意图编号含义1M1M母线2M2M母线Q0变中开关Q11M母线刀闸Q22M母线刀闸Q9主变刀闸Q51开关靠母线侧地刀Q52开关靠CT侧地刀Q8变中地刀Q62B开关靠主变刀闸Q53C变高地刀Q6C变高靠主变侧刀闸Q9S变低刀闸逻辑关系1.变中开关Q0闭锁逻辑:分闸合闸无条件。2.变中母线侧刀闸Q1(或Q2)闭锁逻辑:合闸条件:a.1M(2M)所有地刀分、主变变中开关Q0分,变中开关两侧地刀Q51、Q52分,2M(1M)刀闸Q2(Q1)分;b.2M(1M)刀闸Q2(Q1)合,220kV母联开关及其两侧刀闸合。分闸条件:a.主变变中开关Q0分,2M(1M)刀闸Q2(Q1)分;b.2M(1M)侧刀闸Q2(Q1)合,220kV母联开关及其两侧刀闸合。3.变中主变侧刀闸Q9闭锁逻辑:合闸条件:主变变中开关Q0分,主变变中开关两侧地刀Q51、Q52分,主变三侧地刀(地线)Q8、Q53C、T0-D分;分闸条件:主变变中开关Q0分。4.主变变中主变侧地刀Q8闭锁逻辑:合闸条件:主变变高靠主变侧刀闸Q6C分,B开关靠主变刀闸Q62分,主变变中Q9刀闸分,主变变低刀闸Q9S在分闸位置;分闸条件:无。5.主变变中开关两侧地刀Q51、Q52闭锁逻辑:合闸条件:主变变中两侧刀闸Q1、Q2、Q9分;分闸条件:无。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录D220kV主变典型逻辑关系(双母分段接线方式)接线类别220kV主变典型逻辑关系(双母分段接线方式)接线示意图编号含义1M1M母线2M2M母线Q0EQ0Y变高、变中开关Q1EQ1Y变高变中1M母线刀闸Q2EQ2Y变高变中2M母线刀闸Q9EQ9Y变高变中主变侧刀闸Q51EQ51Y变高变中开关靠母线侧地刀Q52EQ52Y变高变中开关靠CT侧地刀Q9S变低刀闸Q8EQ8Y变高变中主变侧地刀T0-D变低主变侧地线逻辑关系1.主变变高1M(2M)刀闸Q1E(Q2E)闭锁逻辑:合闸条件:a.1M(2M)所有地刀分,主变变高开关Q0E分,变高两侧地刀Q51E、Q52E分,2M(1M)刀闸Q2E(Q1E)分;b.2M(1M)刀闸Q2E(Q1E)合,220kV母联开关及其两侧刀闸合。分闸条件:a.主变变高开关Q0E分,2M(1M)刀闸Q2E(Q1E)分;b.2M(1M)侧刀闸Q2E(Q1E)合,220kV母联开关及其两侧刀闸合。2.主变变中1M(2M)刀闸Q2Y(Q1Y)闭锁逻辑:合闸条件:a.1M(2M)所有地刀分,主变变中开关Q0Y分,变中两侧地刀Q51Y、Q52Y分,2M(1M)刀闸Q2Y(Q1Y)分;b.2M(1M)刀闸Q2Y(Q1Y)分,110kV母联开关及其两侧刀闸合,变中两侧地刀Q51Y、Q52Y分。分闸条件:a.主变变中开关DL2分,2M(1M)刀闸Q2Y(Q1Y)分;b.2M(1M)侧刀闸Q2Y(Q1Y)合,110kV母联开关及其两侧刀闸合。3.变高主变侧刀闸Q9E闭锁逻辑:合闸条件:主变变高开关Q0E分,主变变高开关两侧地刀Q51E、Q52E分,主变三侧地刀(地线)Q8E、Q8Y、T0-D分;分闸条件:主变变高开关Q0E分。4.变中主变侧刀闸Q9Y闭锁逻辑:合闸条件:主变变中开关Q0Y分,主变变中开关两侧地刀Q51Y、Q52Y分,主变三侧地刀(地线)Q8E、Q8Y、T0-D分;37
分闸条件:主变变中开关Q0Y分。5.主变变低刀闸Q9S闭锁逻辑:合闸条件:主变三侧地刀(地线)Q8E、Q8Y、T0-D分,主变变低小车开关在非工作位置;分闸条件:主变变低小车开关在非工作位置。6.主变变高主变侧地刀Q8E闭锁逻辑:合闸条件:主变变高刀闸Q9E分,主变变中Q8Y刀闸分,主变变低刀闸Q9S在分闸位置;分闸条件:无。7.主变变中主变侧地刀Q8Y闭锁逻辑:合闸条件:主变变高刀闸Q9E分,主变变中Q8Y刀闸分,主变变低刀闸Q9S在分闸位置;分闸条件:无。8.主变变低主变侧地线闭锁逻辑T0-D:合闸条件:主变变高刀闸Q9E分,主变变中Q8Y刀闸分,主变变低刀闸Q9S在分闸位置;分闸条件:无。9.主变中性点地刀闭锁逻辑:无条件分合闸。10.主变三侧开关闭锁逻辑:无条件分合闸。11.主变变低开关小车闭锁逻辑:推入工作位置:变低开关在分闸位置,主变三侧地刀(地线)在分闸位置,所在低压侧母线地刀在分闸位置;拉出非工作位置:变低开关在分闸位置。12.主变变高开关两侧地刀Q51E、Q52E闭锁逻辑:合闸条件:主变变高两侧刀闸Q1E、Q2E、Q9E分;分闸条件:无。13.主变变中开关两侧地刀Q51Y、Q52Y闭锁逻辑:合闸条件:主变变高两侧刀闸Q1Y、Q2Y、Q9Y分;分闸条件:无。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录E220kV(110kV)线路典型逻辑关系(双母分段接线方式)接线类别220kV(110kV)线路典型逻辑关系(双母分段接线方式)接线示意图B0DLC02G1G404G编号含义1M1M母线2M2M母线DL开关1G1M母线刀闸2G2M母线刀闸4G线路刀闸B0开关靠母线侧地刀C0开关靠CT侧地刀40线路地刀逻辑关系1.线路开关DL闭锁逻辑:分闸合闸无条件。2.母线侧刀闸1G(或2G)闭锁逻辑:分闸条件:a.线路开关DL分,母线侧刀闸2G(或1G)分;b.母线侧刀闸2G(或1G)合,母联(分段)开关及其两侧刀闸合。合闸条件:a.1M(或2M)所有地刀分,线路开关及其两侧地刀分,2M(或1M)刀闸分;b.2M(1M)刀闸合,母联开关及其两侧刀闸合。3.线路刀闸4G闭锁逻辑:合闸条件:线路开关DL及其两侧地刀分,出线线路地刀分;分闸条件:线路开关分。4.开关两侧接地刀闸B0(或C0)闭锁逻辑:分闸条件:无;合闸条件:出线开关两侧刀闸1G、2G、4G分。5.线路地刀40闭锁逻辑:分闸条件:无;合闸条件:出线线路刀闸4G分、出线线路无压。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录F35kV侧典型逻辑关系(单母接线方式)接线类别35kV侧典型逻辑关系(单母接线方式)接线示意图Q40Q104DLQ202DLPT0PT1DL1G2G3GQ303DL4GG编号含义1M1M母线PTPT刀闸Q15母线地刀PT0PT地刀1DL电抗器开关1G电抗器刀闸Q10电抗器地刀2DL站用变开关2G站用变刀闸Q20站用变地刀3DL电容器组开关3G电容器组刀闸Q30电容器组地刀Q52电容器进线地刀4DL主变开关4G主变刀闸Q40主变地刀逻辑关系1.母线地刀Q15闭锁逻辑:合闸条件:母线上所有刀闸在分闸位置,主变刀闸4G在分闸位置;分闸条件:无。2.PT刀闸闭锁逻辑:合闸条件:母线所有地刀(地线)在分闸位置,PT地刀在分闸位置;分闸条件:无。3.PT地刀闭锁逻辑:合闸条件:PT刀闸分;分闸条件:无。4.电抗器开关1DL闭锁逻辑:无条件。5.电抗器刀闸1G闭锁逻辑:分闸条件:无;合闸条件:母线所有地刀(地线)在分闸位置,电抗器地刀Q10在分闸位置,电抗器开关1DL在分闸位置。6.电抗器地刀Q10闭锁逻辑:分闸条件:无;合闸条件:电抗器刀闸1G分。7.站用变开关2DL闭锁逻辑:无条件。8.站用变刀闸2G闭锁逻辑:分闸条件:无;合闸条件:母线所有地刀(地线)在分闸位置,站用变地刀Q20在分闸位置,站用变开关2DL在分闸位置。9.站用变地刀Q20闭锁逻辑:37
分闸条件:无;合闸条件:站用变刀闸2G分。10.电容器组开关3DL闭锁逻辑:无条件。11.电容器组刀闸3G闭锁逻辑:分闸条件:无;合闸条件:母线所有地刀(地线)在分闸位置,电容器组地刀Q30在分闸位置,电容器进线地刀Q52在分闸位置,电容器开关3DL在分闸位置。12.电容器组地刀Q30闭锁逻辑:分闸条件:无;合闸条件:电容器刀闸3G分。13.电容器进线地刀Q52闭锁逻辑:分闸条件:无;合闸条件:电容器刀闸3G分。14.主变开关4DL闭锁逻辑:无条件。15.主变刀闸4G闭锁逻辑:分闸条件:无;合闸条件:母线所有地刀(地线)在分闸位置,主变地刀Q40在分闸位置,主变开关4DL在分闸位置,主变各侧地刀(地线)在分闸位置。16.主变地刀Q40闭锁逻辑:分闸条件:无;合闸条件:主变开关DL分,主变刀闸4G分。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录G220kV(110kV)母线地刀和PT间隔典型逻辑关系接线类别220kV(110kV)母线地刀和PT间隔典型逻辑关系接线示意图221乙0221甲0222甲0221PT0222PT221PT222乙0222PT0编号含义1M1M母线2M2M母线221PT1母PT222PT2母PT221PT01母PT地刀222PT02母PT地刀221甲01母甲地刀222甲02母甲地刀221乙01母乙地刀222乙02母乙地刀逻辑关系1.母线地刀(221甲0、222甲0、221乙0、222乙0)闭锁逻辑:分闸条件:无条件;合闸条件:地刀所在母线上所有隔离开关分开。2.母线PT刀闸(221PT、222PT)闭锁逻辑:分闸条件:无条件;合闸条件:a.所在母线地刀分,PT地刀分。3.PT地刀(221PT0、222PT0)闭锁逻辑:合闸条件:PT刀闸分;分闸条件:无条件。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录H220kV(110kV)母联或分段间隔典型逻辑关系接线类别220kV(110kV)母联或分段间隔典型逻辑关系接线示意图B0C02MDL1G2G编号含义1M1M母线2M2M母线DL分段开关1G1M母线刀闸2G2M母线刀闸B0开关靠1M母线侧地刀C0开关靠CT侧地刀逻辑关系1.分段开关DL闭锁逻辑:分闸合闸无条件。2.母线侧刀闸1G(或2G)闭锁逻辑:分闸条件:a.分段开关DL分;合闸条件:a.1M(或2M)所有地刀分,分段开关及其两侧地刀分。3.开关两侧接地刀闸B0(或C0)闭锁逻辑:分闸条件:无;合闸条件:分段开关两侧刀闸1G、2G分。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录I220kV(110kV)线路典型逻辑关系(双母带旁路接线类型)接线类别220kV(110kV)线路典型逻辑关系(双母带旁路接线类型)接线示意图DL1M2M1G2GB0C04G3G403M编号含义1M1M母线2M2M母线3M3M母线(旁路母线)DL开关1G1M母线刀闸2G2M母线刀闸3G3M母线刀闸(旁路刀闸)4G线路刀闸B0开关靠母线侧地刀C0开关靠CT侧地刀40线路地刀逻辑关系1.线路开关DL闭锁逻辑:无条件分合闸。2.母线侧刀闸1G(或2G)闭锁逻辑:分闸条件:a.线路开关DL分,母线侧刀闸2G(或1G)分;b.母线侧刀闸2G(或1G)合,母联开关及其两侧刀闸合。合闸条件:a.1M(或2M)所有地刀分,线路开关及其两侧地刀分,2M(或1M)刀闸分;b.2M(1M)刀闸合、母联开关及其两侧刀闸合。3.旁路母线侧刀闸3G闭锁逻辑::合闸条件:3M所有地刀分,旁路开关分,出线线路地刀40分;分闸条件:旁路开关分。4.线路侧刀闸4G闭锁逻辑:合闸条件:线路开关DL及其两侧地刀分,出线线路地刀40分;分闸条件:线路开关分。5.开关两侧地刀B0(C0)闭锁逻辑:分闸条件:无;合闸条件:出线开关两侧刀闸1G、2G、4G分。6.线路地刀闭锁逻辑:分闸条件:无;合闸条件:旁路3M刀闸3G分,出线线路刀闸4G分,出线线路无压。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录J220kV(110kV)专用旁路间隔典型逻辑关系(双母带旁路接线类型)接线类别220kV(110kV)专用旁路间隔典型逻辑关系(双母带旁路接线类型)接线示意图2M1M编号含义1M1M母线2M2M母线3M3M母线(旁路母线)DL开关1G1M母线刀闸2G2M母线刀闸3G3M母线刀闸(旁路刀闸)B0旁路开关靠母线侧地刀C0旁路开关靠CT侧地刀2G1G3M3GC0B0DL逻辑关系1.旁路1M、2M刀闸闭锁逻辑:合闸条件:a.旁路开关DL分,旁路开关两侧地刀B0、C0分,1M(2M)地刀分,2M(1M)刀闸分;b.2M(1M)刀闸合,母联开关及其两侧刀闸合。分闸条件:a.旁路开关分,旁路2M(1M)刀闸分;b.旁路2M(1M)刀闸合,母联开关及其两侧刀闸合。2.旁路3M刀闸闭锁逻辑:合闸条件:3母所有地刀分,旁路开关分,开关两侧地刀B0、C0分;分闸条件:旁路开关分。3.旁路开关两侧接地刀闸B0(或C0)闭锁逻辑:合闸条件:旁路开关两侧刀闸1G、2G、3G分;分闸条件:无。4.旁路开关闭锁逻辑:无条件分合闸。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录K双母带旁路类接线:主变间隔逻辑关系接线类别双母带旁路类接线:主变间隔逻辑关系接线示意图1M1M母线2M2M母线3M3M母线(旁路母线)DL1DL2变高、变中开关1G1G11M母线刀闸2G2G12M母线刀闸3G3G13M母线刀闸4G4G1主变侧刀闸B0B01开关靠母线侧地刀C0C01开关靠CT侧地刀G变低刀闸小车DL3变低小车开关T0T01变高变中主变侧地刀T0-D变低主变侧地线G逻辑关系1.主变变高1M(2M)刀闸1G(2G)闭锁逻辑:合闸条件:a.1M(2M)所有地刀分,主变变高开关DL1分,变高两侧地刀B0、C0分,2M(1M)刀闸2G(1G)分;b.2M(1M)刀闸2G(1G)合,220kV母联开关及其两侧刀闸合。分闸条件:a.主变变高开关DL1分,2M(1M)刀闸2G(1G)分;b.2M(1M)侧刀闸2G(1G)合,220kV母联开关及其两侧刀闸合。2.主变变中1M(2M)刀闸1G1(2G1)闭锁逻辑:合闸条件:a.1M(2M)所有地刀分,主变变中开关DL2分,变中两侧地刀B01、C01分,2M(1M)刀闸2G1(1G1)分;b.2M(1M)刀闸2G1(1G1)分,110kV母联开关及其两侧刀闸合。分闸条件:a.主变变中开关DL2分,2M(1M)刀闸2G1(1G1)分;b.2M(1M)侧刀闸2G1(1G1)合,110kV母联开关及其两侧刀闸合。3.主变变高3M刀闸3G闭锁逻辑:合闸条件:220kV旁路开关分,主变三侧地刀(地线)T0、T01、T0-D分,220kV3M所有地刀分;分闸条件:220kV旁路开关分。4.主变变中3M刀闸3G1闭锁逻辑:合闸条件:110kV旁路开关分,主变三侧地刀(地线)T0、T01、T0-D分,110kV3M所有地刀分;分闸条件:110kV旁路开关分。5.变高主变侧刀闸4G闭锁逻辑:37
合闸条件:主变变高开关DL1分,主变变高开关两侧地刀B0、C0分,主变三侧地刀(地线)T0、T01、T0-D分;分闸条件:主变变高开关DL1分。6.变中主变侧刀闸4G1闭锁逻辑:合闸条件:主变变中开关DL2分,主变变中开关两侧地刀B01、C01分,主变三侧地刀(地线)T0、T01、T0-D分;分闸条件:主变变中开关DL2分。7.主变变低刀闸小车G闭锁逻辑:合闸条件:主变变高地刀T0分,主变变中地刀TO1分,主变变低地线T0-D分,主变变低小车开关在非工作位置;分闸条件:主变变低小车开关在非工作位置。8.主变变高主变侧地刀T0闭锁逻辑:合闸条件:主变变高刀闸3G、4G分,主变变中3G1、4G1刀闸分,主变变低开关小车拉至非工作位置;分闸条件:无。9.主变变中主变侧地刀T01闭锁逻辑:合闸条件:主变变中刀闸3G1、4G1分,主变变高3G、4G刀闸分,主变变低开关小车拉至非工作位置;分闸条件:无。10.主变变低主变侧地线闭锁逻辑T0-D:合闸条件:主变低压侧开关小车在非工作位置,主变变低刀闸小车G在非工作位置,主变变高(变中)主变侧刀闸4G、3G(4G1、3G1)分;分闸条件:无。11.主变中性点地刀闭锁逻辑:无条件分合闸。12.主变三侧开关DL1、DL2、DL3闭锁逻辑:无条件分合闸。13.主变变低DL3开关小车闭锁逻辑:推入工作位置:变低开关在分闸位置,主变三侧地刀(地线)在分闸位置,所在低压侧母线地刀在分闸位置;拉出非工作位置:变低开关在分闸位置。14.主变变高开关两侧地刀B0、C0闭锁逻辑:合闸条件:主变变高两侧刀闸1G、2G、4G分;分闸条件:无。15.主变变中开关两侧地刀B01、C01闭锁逻辑:合闸条件:主变变中开关两侧刀闸1G1、2G1、4G1分;分闸条件:无。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录L单母分段小车开关类型接线:10kV(35kV)线路、分段典型逻辑关系接线类别单母分段小车开关类型接线:10kV(35kV)线路、分段典型逻辑关系接线示意图编号含义1M1M母线2M2M母线DL开关40线路地刀G母线隔离刀闸线路1M40DLDL1M2MG分段逻辑关系线路间隔:1.线路开关DL闭锁逻辑:无条件分合闸。2.线路开关DL小车闭锁逻辑:推入工作位置:线路开关DL在分闸位置,所在母线地刀在分闸位置,线路地刀40在分闸位置;拉出非工作位置:线路开关DL在分闸位置。3.线路地刀40闭锁逻辑:合闸:线路开关小车在非工作位置,线路无电;分闸:无条件。母线分段间隔:1.分段开关闭锁逻辑:无条件分合闸。2.分段开关小车闭锁逻辑:推入工作位置:分段开关DL在分闸位置,两段母线地刀均在分闸位置;拉至非工作位置:开关在分闸位置。3.母线隔离刀闸G闭锁逻辑:推入工作位置:分段开关DL小车在非工作位置,两段母线地刀均在分闸位置;拉至非工作位置:分段开关DL小车在非工作位置。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录M单母分段小车开关接线类型:电容器组及其网门典型逻辑关系接线类别单母分段小车开关接线类型:电容器组及其网门典型逻辑关系接线示意图编号含义1M1M母线DL开关40出线地刀C0电容器组进线地刀(地线)D0电容器组中性点地刀(地线)WM网门逻辑关系1.开关DL闭锁逻辑:无条件分合闸。2.开关小车闭锁逻辑:推入工作位置:开关DL在分闸位置,所在母线地刀在分闸位置,出线地刀40在分闸位置,电容器组进线地刀C0分,电容器组中性点地刀D0分;拉至非工作位置:开关在分闸位置。3.出线地刀40闭锁逻辑:合闸:开关小车在非工作位置;分闸:无条件。4.电容器组进线地刀闭锁逻辑:合闸:开关小车在非工作位置;分闸:无条件。5.电容器组中性点地刀闭锁逻辑:合闸:开关小车在非工作位置;分闸:无条件。6.网门闭锁逻辑(有C0、D0地刀):打开:出线地刀40在合闸位置,电容器组两侧地刀C0、D0在合闸位置;关上:无条件。7.网门闭锁逻辑(无C0、D0地刀,需接地线):打开:出线地刀40在合闸位置;关上:电容器组两侧地线C0、D0在分闸位置。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
接线类别单母分段小车开关接线类型:站变(接地变)及其网门典型逻辑关系接线示意图编号含义1M1M母线DL站变变高开关40出线地刀40-D站变变高侧接地线T0-D站变变低接地线WM网门ZK变低开关逻辑关系1.站变变高开关DL闭锁逻辑:无条件分合闸。2.站变变高开关DL小车闭锁逻辑:推入工作位置:开关DL在分闸位置,所在母线地刀在分闸位置,出线地刀40在分闸位置,站变两侧地线40-D、T0-D在分闸位置;拉出非工作位置:开关在分闸位置。3.出线地刀40闭锁逻辑:合闸:开关DL小车在非工作位置,站变低压侧开关ZK在分闸位置;分闸:无条件。4.站变变高侧接地线40-D闭锁逻辑:合闸:开关DL小车在非工作位置,ZK在分闸位置;分闸:无条件。5.站变变低接地线T0-D闭锁逻辑:合闸:开关小车在非工作位置,ZK在分闸位置;分闸:无条件。6.站变低压侧开关ZK闭锁逻辑:合闸:站变两侧接地线40-D,T0-D在分闸位置,出线地刀40在分闸位置;分闸:无条件。7.网门闭锁逻辑:打开:站变出线地刀在合闸位置,ZK在分闸位置;关上:站变两侧接地线40-D、T0-D在分闸位置。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。附录N单母分段小车开关接线类型:站变(接地变)及其网门典型逻辑关系37
附录O单母分段带旁路接线类型:出线、分段、旁路间隔典型逻辑关系接线类别单母分段带旁路接线类型:出线、分段、旁路间隔典型逻辑关系接线示意图编号含义1M1M母线2M2M母线3M3M母线(旁路母线)DL线路开关2DL分段开关3DL旁路开关1G出线间隔1M母侧刀闸4G出线间隔线路侧刀闸3G出线间隔3M母侧刀闸1G2分段开关1M母侧刀闸2G2分段开关2M母侧刀闸3G2旁路开关2M母侧刀闸3G3旁路开关3M母侧刀闸2DL3DL3G33G22G21G23M3GDL2M1M4G1G逻辑关系线路间隔:1.线路开关DL闭锁逻辑:无条件分合闸。2.出线间隔1M母侧刀闸1G闭锁逻辑:分闸条件:线路开关DL分;合闸条件:线路开关DL分,线路开关两侧地刀在分,所在母线地刀分。3.出线间隔线路侧刀闸4G闭锁逻辑:分闸条件:线路开关DL分;合闸条件:线路开关DL分,线路开关两侧地刀在分,线路地刀在分。4.本出线间隔3M母侧刀闸3G闭锁逻辑:分闸条件:旁路开关3DL分闸;合闸条件:旁路开关3DL在分闸位置,3M上所有地刀在分闸位置,线路地刀在分闸位置。旁路间隔:1.旁路开关3DL闭锁逻辑:无条件分合闸。2.旁路间隔2M母侧刀闸3G2闭锁逻辑:分闸条件:旁路开关3DL分;合闸条件:旁路开关3DL分,旁路开关两侧地刀在分,所在母线地刀分。3.旁路间隔3M母侧刀闸3G3闭锁逻辑分闸条件:旁路开关3DL分闸;合闸条件:旁路开关3DL分闸,旁路开关两侧地刀在分,旁路母线上所有地刀分。分段间隔:1.分段开关2DL闭锁逻辑:无条件分合闸。2.分段开关1M(2M)母侧刀闸1G22G2闭锁逻辑:分闸条件:分段开关2DL分;合闸条件:分段开关2DL分,分段开关两侧地刀在分,两段母线上所有地刀在分闸位置。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录P线路变压器组接线图:线变组典型逻辑关系接线类别线路变压器组接线图:线变组典型逻辑关系接线示意图DL4GC0T0401DL1T0-D编号含义DL线路开关4G线路刀闸40线路地刀C0开关CT侧地刀T0T0主变变高地刀1DL变低小车开关1T0-D变低地线逻辑关系1.主变高压侧出线线路地刀40闭锁逻辑:合闸条件:出线线路刀闸4G分,线路无压;分闸条件:无。2.主变高压侧出线线路刀闸4G闭锁逻辑:合闸条件:出线线路DL开关分,出线线路地刀40分,出线开关CT侧C0,主变两侧地刀(地线)T0、1T0-D分;分闸条件:出线线路开关DL分。3.主变高压侧出线开关CT侧地刀C0闭锁逻辑:合闸条件:出线线路刀闸4G分,主变低压侧开关1DL小车在非工作位置;分闸条件:无。4.主变变高地刀T0闭锁逻辑:合闸条件:主变变低开关1DL小车在非工作位置,出线线路刀闸4G分;分闸条件:无。5.主变低压侧小车开关1DL闭锁逻辑:无条件分合闸6.主变低压侧开关1DL小车闭锁逻辑:推入工作位置条件:主变变低开关1DL分,主变两侧地刀(地线)T0、1T0-D分,变低开关1DL所在母线所有地刀分;拉至非工作条件:主变变低开关分。7.主变变低接地线1T0-D闭锁逻辑:合闸条件:高压侧出线线路刀闸4G分,主变变低开关1DL小车在非工作位置;分闸条件:无。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录Q桥型接线类:110kV桥型接线典型逻辑关系接线类别桥型接线类:110kV桥型接线典型逻辑关系接线示意图1M1M母线2M2M母线DL1线路1开关DL2线路2开关DL3母联开关1G线路1的1M刀闸1G2#1主变变高刀闸2G1线路2的2M刀闸2G2#2主变变高刀闸MG1MG2母联开关1M2M刀闸B0B01线路开关靠母线侧地刀C0C01线路开关靠CT侧地刀4G4G1线路刀闸40401线路地刀1M-D2M-D母线地刀(地线)逻辑关系1.110KV线路线路40401地刀闭锁逻辑:合闸条件:出线线路刀闸分,线路无压;分闸条件:无。2.110KV线路母线侧刀闸1G(2G1)闭锁逻辑:合闸条件:线路开关DL1(DL2)分,线路开关两侧地刀B0、C0(B01、C01)分,本母线地刀1M-D(2M-D)分;分闸条件:线路开关分。3.110KV线路线路刀闸4G(4G1)闭锁逻辑:合闸条件:线路开关DL1(DL2)分,线路开关两侧地刀B0、C0(B01、C01)分,线路地刀40(401)分;分闸条件:线路开关DL1(DL2)分。4.110KV线路开关两侧地刀B0、C0(B01、C01)闭锁逻辑:合闸条件:线路开关两侧刀闸1G、4G(2G1、4G1)分;分闸条件:无。5.110KV母线地刀1M-D2M-D闭锁逻辑:合闸条件:接在本母线上的所有刀闸1G、1G2、MG1(2G1、2G2、MG2)分;分闸条件:无。6.主变变高刀闸1G22G2闭锁逻辑:合闸条件:110KV本母线地刀分,主变各侧地刀分;分闸条件:线路开关DL1和母联开关DL3在分闸位置。7.母联开关、线路开关闭锁逻辑:无条件分合闸。8.母联开关靠1M(2M)侧刀闸闭锁逻辑:合闸条件:所在母线上所有地刀在分闸位置,母联开关在分闸位置,母联开关两侧地刀在分闸位置;37
分闸条件:母联开关在分闸位置。注:接地线的分合规则与相应位置处的地刀分合通用闭锁逻辑相同。刀闸的闭锁条件中,要考虑接地线对其的闭锁,接地线对刀闸的闭锁与相应位置的地刀对刀闸的闭锁一样。37
附录R接地桩形式图37
附录S接地桩布置图37
附录T接地桩编号原则一、与非母线接地刀闸(如线路侧地刀、开关两侧地刀、主变各侧地刀等)五防逻辑相同且接地点相同的临时接地桩,其编号原则为:“接地刀闸编号”+“-D”。如“236840-D、2368C0-D、2368B0-D、2201T0-D、101T0-D、13940-D、139C0-D、139B0-D、201210-D、201220-D、10010-D、10030-D、222PT0-D、11PT0-D、F21B0-D、F21C0-D、F2140-D等”。二、与母线接地刀闸五防逻辑相同且接地点相同的临时接地桩,其编号原则为:“接地刀闸编号”+“-MD”。如“221甲00-MD、221乙00-MD、111甲0-MD、112甲0-MD等”。三、如果在某刀闸靠母线侧装设的临时接地桩,五防逻辑与母线接地刀闸相同但接地点不相同的临时接地桩,其编号原则为:“刀闸编号”+“-MD”。如“23681-MD、23682-MD、23683-MD、1391-MD等”。四、10KV母线装设的临时接地桩,其编号原则为:“主变变低开关编号”+“-母线号+MD”例如“500-1MD、500-2MD、501-1MD、502-2MD、503-3MD、501A-1AMD、501B-1BMD、502A-2AMD、502B-2BMD(主变变低有两台开关供不同母线)等”。五、主变变低母线桥装设的临时接地桩,其编号原则为:“变低开关编号”+“T0”+“-D”。如“501T0-D、502T0-D等”。六、电容器组在串联电抗器进线电缆头、电容器进线电缆头或电容器中性点处装设的临时接地桩,五防逻辑与对应的接地刀闸相同但接地点不相同的临时接地桩,其编号原则为:“电容器接地刀闸编号”+“-D”。如“51140-D、511C0-D、521D0-D等”。七、在站变、站变兼接地变或接地变高压侧电缆头处装设的临时接地桩,其编号原则为:“站变或接地变变高开关接地刀闸编号”+“-D”。如“51040-D等”。八、在接地变低压侧电缆头处装设的临时接地桩,其编号原则为:“所在高压侧开关编号”+“L0”+“-D”。如“510L0-D等”。九、在站变、站变兼接地变低压侧电缆头处装设的临时接地桩,其编号原则为:“站变、站变兼接地变低压侧开关编号”+“-D”。如“1ZK-D等”。十、线路耦合电容器或电压式互感器靠线路出变电站侧临时接地桩,其编号原则为:“线路接地刀闸编号”+“-0D”。如“14040-0D等”。十一、一般同一个电气连接部分只设一个临时接地桩,如果同一个电气连接部分有多个临时接地桩的,可在上述编号后面增加序列号,其他不变,如110kV及以上线路的线路侧接地点出线地刀下方接地桩编号为“236840-D1”,110kV及以上线路避雷器高压侧接地桩编号为“236840-D2”。规定序列号的递增方向为出线方向。十二、以上临时接地桩编码原则暂不适用于500kV设备。39'